Genset FG Wilson 275 kVA
Genset FG Wilson 275 kVA
Specifications
Minimum Rating
230 kVA / 184 kW
Maximum Rating
250 kVA / 200 kW
Emissions/Fuel Strategy
Fuel Optimised
Description
Genset FG Wilson 275 kVA
BELIALAT.COM support penjualan unit, parts, service, rental, maintenance contract, overhaul, reconditioned Genset FG Wilson 275 kVA
Features
The FG Wilson 275 kVA genset has the following features:
Reliable Power Generation:
– Designed to provide reliable power generation for various applications
– Suitable for industrial, commercial, and residential use.
Advanced Control System:
– Deep Sea or PowerWizard control panel for easy monitoring and control
– Advanced features for automatic control, monitoring, and protection.
Fuel Efficiency:
– Designed to be fuel-efficient, reducing operating costs and environmental impact.
Robust Construction:
– Built with a robust steel base frame for durability
– Captive linear vibration isolators between base and engine-generator.
Noise Reduction:
– Available in silent or sound-attenuated versions, suitable for residential areas.
Optional Equipment:
– Industrial, residential, and critical silencers
– Quadrature droop kit.
– Anti-condensation heater and panel circuitry
– AREP / PMG excitation.
Easy Maintenance:
– Designed for easy maintenance and service
– Accessible components for quick and efficient maintenance.
Some possible specifications for the FG Wilson 275 kVA genset include:
– Engine: Perkins or similar diesel engine (e.g., Perkins 1104A-44TAG2)
– Alternator: Stamford or Leroy Somer brushless alternator.
– Voltage: 220-415V
– Frequency: 50Hz
These features and specifications are designed to provide reliable and efficient power generation, while minimizing downtime and operating costs. The specific features and specifications may vary depending on the model and configuration.
Specifications
Minimum Rating
250 kVA / 200 kW
Maximum Rating
275 kVA / 220 kW.
Emissions/Fuel Strategy
EUIIIa Emissions Compliant
General
Minimum Rating : 250 kVA / 200 kW
Maximum Rating : 275 kVA / 220 kW
Emissions Fuel Strategy : EUIIIa Emissions Compliant
50 Hz Prime : 250 kVA / 200 kW
50 Hz Standby : 275 kVA / 220 kW
60 Hz PrimeĀ : –
60 Hz Standby : –
Frequency : 50
Speed : 1500 rpm
Voltage :115-415 Volts
50 Hz Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
60 Hz Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
50 Hz Standby Rating
Standard reference conditions 25C (77F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Engine
Engine Model : Perkins 1506D-E88TAG4
Bore : 112 mm (4.4 in)
Stroke : 149 mm (5.9 in)
Governor Type : Electronic
Displacement : 8.8 (57 cu. in)
Compression Ratio : 16.1:1
Reviews