Genset FG Wilson 175 kVA
Genset FG Wilson 175 kVA
Specifications
Minimum Rating
160 kVA / 128 kW
Maximum Rating
175 kVA / 140 kW
Emissions/Fuel Strategy
EU Stage IIIA emissions compliant.
Description
Genset FG Wilson 175 kVA
BELIALAT.COM support penjualan unit, parts, service, rental, maintenance contract, overhaul, reconditioned Genset FG Wilson 175 kVA
Specifications
Minimum Rating
160 kVA / 128 kW
Maximum Rating
175 kVA / 140 kW
Emissions/Fuel Strategy
EU Stage IIIA emissions compliant.
General
Minimum Rating : 160 kVA / 128 kW
Maximum Rating : 175 kVA / 140 kW
Emissions Fuel Strategy : EU Stage IIIA emissions compliant.
50 Hz Prime : 160 kVA / 128 kW
50 Hz Standby : 175 kVA / 140 kW
60 Hz PrimeĀ : –
60 Hz Standby : –
Frequency : 50 Hz
Speed : 1500 RPM
Voltage :220-415 Volts
50 Hz Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in lieu of commercially purchased power. There is no limitation to the annual hours of operation and this model can supply 10% overload power for 1 hour in 12 hours.
60 Hz Prime Rating
These ratings are applicable for supplying continuous electrical power (at variable load) in the event of a utility power failure. No overload is permitted on these ratings. The alternator on this model is peak continuous rated (as defined in ISO 8528-3).
50 Hz Standby Rating
Standard reference conditions 25C (77F) Air Inlet Temp, 100m (328 ft) A.S.L. 30% relative humidity. Fuel consumption data at full load with diesel fuel with specific gravity of 0.85 and conforming to BS2869: 1998, Class A2.
Engine
Engine Model Perkins 1106D-E70TAG3
Bore 105 mm (4.1 in)
Stroke 135 mm (5.3 in)
Governor Type Electronic
Displacement 7.0l (427.8 cu. in)
Compression Ratio 16.8:1
Reviews